INTELLIGENT 3Phase Split Monitor to 3 x 32A 1Phase
IT-499-IP5-1L
IT-499-IP5-1L IPower 3Phase splitter IP Monitored 1x32A 3Phase input Power Splitter to ( 3x 32Amp Single Phase outputs )
Designed to be connected to the 3Phase supply output from which 3 x single phase
PDU's would then be connected.
Up to 32 Devices can be daisy chained from a single IP address unit.
The PDU Agent can support up to 50 x IP addresses.
These units in use would require 1 unit per 3 Single Phase PDU,s
Power Monitoring is provided by using a calibrated resistor giving accuracy greater than 1%. Intelligent Power has an easy-to-use HTML interface with the ability to set SMS and Email alarms for all critical parameters. Can be configured as a Primary device, with the ability to control an additional 31 Secondary devices, from a single IP address. Intelligent Power units will work in conjunction with other units to create a fully flexible monitoring system allowing for individual racks to have measurement only, or measurement and switching capabilities PDU Agent ™ Management Software Collate and produce reports on all your readings. PDU Agent is an entry level management platform with easy to use dashboard layout that lets you log measurements and events from multiple units, for historical evaluation and to collate and produce accurate billing information
These options provide more than just power monitoring which may or may not be required now, but many possible benefits including sensors and rack environmental info in the future.
- Connected to the 3phase output from which 3 x single phase outputs for PDU,s would be connected.
Benefits:
- Can buy as little as one unit at a time as required so less upfront costs.
- Free software to produce billing reports.
- Easy plug in installation
- UK manufactured and supported
- Calibrated
resister for power measurement giving the highest level of accuracy.
- All reporting software (PDU Agent) is provided FOC
- UK Technical Support FOC
- Up to 32 units can be daisy chained over a single IP address
- The Device PDU Agent can support up to 50 x IP addresses
- Can supply with flying leads as opposed to fixed sockets if required POA
- Would require 1 unit per 3 single phase PDU,s
- 5 Year Warranty Return to base
Energy metrics including:
• Volts
• Watts
• Amps
• Power factor
• kWh
• Frequency
• VA
• kVA
• Peak Volts
• Peak Amps
• Internal Temp
• Kg/Co2
• KJ/H
• BTU/H
Environmental & security
metrics including::
• Up to 8 Temperature sensors
• Single temp/humidity sensor
• 3 sets of dry contacts
• Cabinet door lock
• Card reader
• Door open sensor
• Remote display
• MOD BUS port
• USB port
Communications & Protocols:
• HTTP
• HTTPS
• HTML
• CGI
• TELNET
• SMTP
• SYSLOG,
• RADIUS,
• SNMP v2 v3
• IP v4 v6
IT-499-IP5-1L IPower 3Phase splitter 1x 400v 32A 3Phase in 3x 230v 32A Single phase out. ( 3Phase power splitter )
Body Dimensions: 270mm Wide 80mm Deep 350mm Long TBC
Fixing Centres:
Material: Sheet MS
Finish: Black powder coat
Fixing Method: End Brackets
Input: 1mtr 5core 6mm HO7 cable to 32A 3PH Commando
Output: 3x32A Commando sockets
Protection: 32A MCB
Indicator: Front display, individual outlet power present
Earthing: M6 Earth stud to end
Rating: 32A @ 400V AC 50/60 Hz
Standards: Conforms to BS EN60950-1:2005 2nd edition +AM1 & AM2
Conforms to BS EN62368-1:2014+All:2017
UK CA: Compliant
WEEE: Compliant
RoHS: Compliant
CE: Compliant
Operating Temp: -10° to +60°C depending on protection device.
Warranty: 5 years return to base
INPUT:
Type 3 Phase
RMS Volts 400V
RMS Amps 32A
OUTPUT:
Type 1 Phase
RMS Volts 230V
RMS Amps 32A
PF 0.9
PDU TOTAL
kVA 38.4
kW 34.56
Electrical Rating.
Please note, these calculations are based on an assumed steady voltage of 230V AC and a Power Factor of 0.9. Voltage fluctuations will affect the kVA & kW values. The only rating that is constant is Current (Amps) This PDU will handle a constant current draw up to 63A. The kVA & kW ratings and are for indication purposes only.